ATEN PE9216r User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 13
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
Energy Intelligence Solutions
PE9330B
Connections
Support 10/100Mbit Ethernet Interface
Support TCP/IP, UDP, HTTP, HTTPS, SSL, DHCP, SMTP, ARP,
NTP, DNS, Auto Sense, Ping, SNMP V1,V2&V3
Support 2-level account/password security, IP/MAC filter,
128 bit SSL, RADIOUS
Support : eco Sensors, Browser ( IE, Firefox, Chrome, Safari )
Metering
PDU and outlet level power metering and monitoring
Environment monitoring supports external temperature/
temperature & humidity sensors for rack temperature and
humidity monitoring
Current, voltage, power, power dissipation, temperature,
and humidity metering and threshold level setting
Support door sensor
Outlet Switch Control
Remote power outlet control (On/Off, Power Cycle) by
individual outlets and outlet groups
Outlet group support at the PDU level
Support multiple power control methods – Wake on LAN,
System After AC Back, Kill the Power
Power-On sequencing – users can set the power-
on sequence and delay time for each outlet to allow
equipment to be powered on in the correct order
Critical load outlet – keeps power always on for critical load
devices
Proactive overload protection(POP) – automatically powers
off the last outlet that caused the current overload
Description: 100-240V 30A 0U 30-Outlet PDU
Function: 30-Outlet Metering,
16-Outlet Switching Control &
2-Bank Metering
Input Power Plug: NEMA L6-30P
Power Capacity: 6.2 kW
Socket
Configuration:
IEC 60320 C19 ( 4 )
IEC 60320 C13 (26)
Features
10
Page view 9
1 2 ... 5 6 7 8 9 10 11 12 13

Comments to this Manuals

No comments